1 Fleet Landing Blvd ELPP20-0058 Fire Alarm DRWGSQA A i I A i: oil nnDI� Q�aG3� G���]OOWQ�n noG�] SYMBOL LEGEND ITEM NO. SYMBOL QTY. TOTAL DESCRIPTION MANUFACTURER MODEL BOX REQUIREMENT MOUNTING HEIGHT 1 ® 3 CONTROL RELAY SIEMENS HTRI—R 4" SQUARE FIELD VERIFY 2 ® 3 PULL STATION SIEMENS HMS—D 4" SQUARE 48" A.F.F. TO TOP 3 ® 1 SMOKE DETECTOR SIEMENS HFP-11 OCTAGONAL CEILING MOUNTED 4 CM< 1 CEILING MOUNTED HORN/STROBE SIEMENS SLHSCW-F 4" SQUARE DEEP CEILING MOUNTED WIRE LEGEND WIRE LEGEND T.S.J. = TWISTED SHIELDED JACKETED INDICATOR NO. OF CONDUCTORS SIZE AWG. COLOR WIRE TYPE DESCRIPTION A 2 18 RED FPLR TSJ ADDRESSABLE LOOP B1 2 14 YELLOW FPLR HORN/STROBE CKT. GENERAL NOTES 1. SYSTEM SHALL BE INSTALLED PER NFPA 72 2013, NFPA 90A 2012, NEC 70 2014, IBC 2015, FFPC 6th. EDITION 2017 (INCLUDED IS NFPA 1/101 2015) AND AS PER MANUFACTURERS RECOMMENDATIONS. 2. ALL SMOKE DETECTORS SHALL BE MOUNTED A MINIMUM OF 3 FEET FROM ANY HVAC DIFFUSERS AND TIPS OF FAN BLADES. 3. ALL SHIELDS SHALL BE CONTINUOUS AND FREE OF ANY GROUND LOOPS. SHIELD TERMINATIONS SHALL BE AS PER MANUFACTURERS RECOMMENDATIONS. 4. ALL. WIRING SHALL BE FREE OF IMPROPER SPLICES (4 OR LESS WIRES UNDER 1 WIRE- -NUT). 5. DEVICE AND PANEL LOCATIONS ARE APPROXIMATE. ACTUAL PLACEMENTS TO BE COORDINATED IN FIELD. FINAL PLACEMENTS WILL BE REFLECTED ON AS—BUILT DRAWINGS. 6. ALL JUNCTION BOXES ABOVE THE CEILING CONTAINING FIRE ALARM WIRING SHALL BE MARKED OR PAINTED RED. 7. ALL CEILINGS ARE 10'0" OR LESS AFF UNLESS OTHERWISE NOTED. 8. THE PROVISIONS FOR NEPA 101 39.3.4.2 2015 EDITION ARE MET FOR THE BUILDING. SCOPE OF WORK THE SCOPE OF WORK IS TO INSTALL THE DEVICES PER THE DRAWING TO ACCOMMODATE THE RENOVATIONS. CONNECT NEW ADDRESSABLE DEVICES TO THE EXISTING BUILDING ADDRESSABLE LOOP. CONNECT NEW HORN/STROBE TO THE EXISTING HORN/STROBE CKT. DEVICE ADDRESS/CKT. DESIGNATION (TBD) SHALL BE DETERMINED IN THE FIELD AND REFLECTED ON THE AS—BUILT DRAWINGS. DEVICE IMPACT ON THE EXISTING CKTS. SHALL BE DETERMINED IN THE FIELD AND REFLECTED ON THE AS—BUILT DRAWINGS. ALL WIRING SHALL BE CLASS "B'. OCCUPANCY TYPE THE OCCUPANCY IS RESIDENTIAL SPRINKLER PROTECTION THE BUILDING IS FULLY SPRINKLED. Q r 2131 FROM EXISTING HORN/STROBE CKT. o C 1A TBD TBD TBD TBD TBD TBD TBD FROM EXISTING ADDRESSABLE LOOP ­0� CR P PARTIAL SYSTEM RISER DETAIL SCALE: N.T.S. SUBMITTED BY: ADAM BUCK W.W.GAY FIRE PROTECTION INC. 2251 ROSSELLE STREET JACKSONVILLE, FLORIDA 32204 PHONE: (904) 394-5682 EMAIL: ABuck11 Osciensbuildingsolutions.com SYSTEM SEQUENCE OF OPERATION MATRIX FIRE ALARM SYSTEM SEQUENCE OF OPERATION MATRIX SYSTEM OUTPUTS O� _ SSP•`\ �P�GQ OF SYSTEM INPUTS ��P� ��°�o•GP�°o°�PG�`�°J��`�� ALARMS MANUAL FIRE ALARM STATIONS X X X X X SMOKE DETECTOR X X X X X SYSTEM ALARM X X X X X NOTE: THIS SEQUENCE OF OPERATION REPRESENTS THE WORK BEING PERFORMED IN THE SCOPE SHOWN ON THIS DRAWING ONLY. TBD TBD ® CR - FIRE ALARM LAYOUT PARTIAL FIRST FLOOR SCALE: 1/8"=l' -O" L' NORTH Jacksonvine Fire Prevention Div C L 1 2020 ROBERT L. HINKLE PE 29302 C1 NO EXCEPTIONS POWELL & HINKLE ENGINEERING, P.A. GALTON C. MOK PE 33192 Cl EXCEPTIONS AS NOT'ECt PH 1409 KINGSLEY AVENUE, BLDG 12A LANE R. HINKLE PE 48076 illI-F-r ORANGE PARK, FLORIDA 32073 THOMAS M. ELDER PE 56121 (904) 264-5570 FAX:(904) 278-2646 RICHARD A. MATHEWS PE 59418 >IG G LICENSE NUMBER CA -4577 DAVID R. SPELL JR. PE 54729 JAMES L. HENNESSEY PE 83241 p r ERM �1' u MAIN OFFICE: 2251 ROSSELLE STREET JACKSONVILLE, FL 32204 PHONE: (904)387-7973 FAX: (904) 394-7261 WEBSITE: WWW.*V&'W.COM ECA 001417 GAINESVILLE BRANCH: 2500 N.E. 18TH TERRACE GAINESVILLE, FL 32609 PHONE (352) 387-0.317 FAX: (352) 378-1454 V) z 0 V Of m Ld Q 0 6 z Qp J o > j C U Z CRNM MO LL Z cu ca JN c N m O LJ_ G Z� LL Q QQ�QQ _L J F— J W W Q W J LL LL LL. z 0 U Ld a� � in DATE: DECEMBER 17, 2020 JOB NO: FP -246070 DRAWN BY: CHECKED BY: B.N. I A.B. PROJECT FOLDER: H-20059 FA -01 SHEET 01 OF 01